Nxtension 48V Inverter Print E-mail


                                                                DOWNLOAD DATASHEET

Our Range of Professional DC to AC pure sine wave Inverters, offer you superior performance for a wide range of applications. The Nxtension 48VDC Inverter is most suitable for Telecom applications. The strong engineering work and reliable design will make the Nxtension Inverter your favourite choice anytime. The Nxtension Inverter are designed for a long “working life” and are protected against short circuits, overloading and high temperatures.

    1. Pure Sine Wave
    2. Functional design – 48V Telecom
    3. High surge power output.
    4. Protection against high/low battery voltage, high temperature, overload and short circuit
    5. Automatic standby function to reduce no-load power consumption
    6. Variable speed fan for silent operation
    7. IEC worldwide accepted AC outlet (IEC320 plug included)
    8. 1,5 m. DC connection cable included.
    9. CE and e-mark certified
    10. 24 month warranty
    11. Design for Telecom, small industry and remote home
                                                                                    

The newest available technology brings you an extremely efficient operation with a very low – “no-load” consumption. The Automatic standby function (ASB), it’s a standard in all Nxtension Inverters. It will even reduce the no-load consumption with an extra 70%

Technical specifications

Parameter

Nxt48-200

Nxt48-400

Nxt48-750

Nxt48-1500

Output power¹    Pnom

175VA

300VA

600VA

1000VA

                         P30minutes

200VA

400VA

750VA

1500VA

                         Psurge

400VA

800VA

1250VA

3000VA

Output voltage

230VAC±2% or 115VAC±2%

Output frequency

50Hz±0,05% or 60Hz±0,05%

Output waveform

True sinewave(THD<5%¹ @ Pnom)

Admissible cos φ of load

0,2-1(up to Pnom)

Input voltage (±3% tolerance):         Nominal

48VDC

48VDC

48VDC

48VDC

                         Range

41²-60VDC

41²-60VDC

41²-60VDC

41²-60VDC

Maximum Efficiency

93%

95%

94%

96%

No load consumption [ASB]

<4W [1,2W]

<6,5W [1,3W]

<8,2W [0,5W]

<10,5W [2,5W]

Operating temperature range (ambient)

-20° C to +50° C

ASB threshold

Pout=12W

Pout=15W

Pout=15W

Pout=5W

Protections against

Short circuit, overload, high temperature and low battery voltage

Indications(by pre-programmed flashing sequences of the power LED)

Power on, short circuit/overload, high temperature, high/low battery voltage, ASB mode & high ripple voltage(1500VA only)

DC input connection

Two wires, length 1,5 meters Ø 4mm²

Two wires, length 1,5 meters Ø 10mm²

Two wires, length 1,5 meters Ø 25mm²

AC output connection

IEC-320 outlet

Enclosure body size

154x98x130(without mounting brackets)

184x98x130mm(without mounting bracket)

228x113x163(without mounting brackets)

355x105x206mm(without mounting brackets)

Total weight

2,4 kg

3,5 kg

6,2 kg

11,2 kg

Protection class

IP20

The Inverter complies with the following standard.

EN50081-1(EN55022), EN50082-1(IEC801-2/3/4, EN61000-4-3), LVD 73/23EEC(EN60335-1), e4-95/54/EC, ROHS

 Content may change without further notice – Aug. 2007

 

1)      Measured with resistive load at 25° C. Power ratings are subject to a tolerance of 4% and decreasing as temperature  rises with a rate of approx. 1,2% /° C starting from 25° C.

2)      Under voltage limit is dynamic. This limit decreases with increasing load to compensate the voltage drop across cables and connections.

3)      Measured at nominal input voltage and 25° C.

 